User friendly 500 kw Load Bank Manufacturers in China

Resistive-load bank
Resistive-load bank
Resistive-load bank
Resistive-loadbank
Resistive-loadbank
Resistive-loadbank-500kw-8
Resistive-loadbank-500kw-9
Resistive-loadbank-500kw-10
Resistive-loadbank-500kw-6
Resistive-loadbank-500kw-7
previous arrowprevious arrow
next arrownext arrow
 
Model: KPLB-100
Testing capacity: 0 – 500 kw
Type of load:Resistive, PF = 1.0
Duty: Continuous
Cooling system: Industrial grade axial fan
Phase: Available at both single and three phase
Rated testing voltage: 110-480 VAC
Rated Frequency: 50/60 Hz
Dimensions (LWH)(mm): 1900*1600*1900
Weight: 350 Kg(100kw)

Keep your generator fleet operating efficiently.

load banks technical data

1. Resistive type of load, PF = 1.0. Stainless steel sheathed elements manufactured from high grade magnesium oxide.
2. Rated testing voltage: AC 3P4W, 110-480V 50/60 Hz.
3. Cooling mode: Forced air-cooled, fans mounted on the side of the load bank blow horizontally. Testing power or external utility power supply for fans.
4. Working mode: Load step control
Total testing capacity ranges from 0kw to the max consisting of 10kw, 20kw, 50kw, 100kw load setting switches plus a 0-10kw fine-tuning knob. From 0kw to the max, any load combination is achievable. Load step resolution is 10kw.
5. Load bank features world-famous components to ensure reliable performance and longer service life including:
     SCHNEIDER contactors.
     Siemens switches, knobs and indicators.
     ABB Circuit breakers.
     OMRON intermediate relays.
     PHOENIX terminal blocks.
6.  Parameter measuring accuracy grade: 0.3
7. Load control accuracy: ± 5%.
8.Load bank protections: Over heating protection, cooling fans failure protection and over load protection with alarm.
9. Control mode: Two control modes available:
A)Local manual control;
B)Optional: Manual control via a remote control panel (max control distance is 30m).
10. Parameter display and measurement:
Control panel contains a LOVATO Multifunction Electricity Meter displaying voltage, current, load power, reactive power, apparent power, power factor, frequency etc.
(Optional: A professional generator tester displays and measures all sorts of steady, dynamic parameters as well as harmonic wave, can be connected to a PC for data recording and test report printing). “
11. Operating environment:
Altitude: ≤ 2500m above sea level. Ambient temp: -15~+55 ℃
Relative humidity: 95% ventilated environment without explosive or corrosive dust. Not allowed to use in rainy outdoor environment.