500kW Resistive Load Bank battery banks testing

Resistive-load bank
Resistive-load bank
Resistive-load bank
Resistive-loadbank
Resistive-loadbank
Resistive-loadbank-500kw-8
Resistive-loadbank-500kw-9
Resistive-loadbank-500kw-10
Resistive-loadbank-500kw-6
Resistive-loadbank-500kw-7
previous arrowprevious arrow
next arrownext arrow

Type of load: Resistive, PF = 0.8-1.0
Duty: Continuous
Cooling system: Industrial grade axial fan
Phase: Available at both single and three phase
Rated testing voltage: 110-480 VAC
Rated Frequency: 50/60 Hz

Load bank is a simulating load test equipment used for generators, UPS, battery banks etc power systems load test.

Product Details >>

KEYPOWER GENERATOR TESTER SPECIFICATIONS
Measurement Range Accuracy Resolution Overload
Voltage (V) 10.0~500.0V ± (0.4% reading+0.1%range) 0.1V 600V
Current (A) 0.030~5.000A ± (0.4% reading+0.1%range) 0.001A 6A
Power According to volt range
&  current range
Power factor =1.0 <200W 0.1W
± (0.4% reading+0.1% range) ≥200W 1W
Power factor =0.5 ≥2kW 10W
± (0.8% reading+0.2% range)
Power Factor 0.20~1.00 ±0.02 0.001
Frequency 45~65Hz ±0.2Hz 0.01Hz
Running 45~65Hz ±0.2Hz 0.01Hz
Energy
(kWh)
99999kWh  Power factor= 1.0 0.001kwh
± (0.4% reading+0.1% range)
Power factor=0.5
± (0.8% reading+0.2% range)
Harmonic Analysis
(%)
2-50 times
and total harmonic
Models You Can Choose
Model Testing 
capacity
Type 
of
 load
Duty Cooling 
system
Phase Rated 
Testing 
Voltage
Rated
 Frequency
Dimensions   
   (L*W*H)
 (mm)
Weight
 (kg)
KPLB-125 0 – 100 kw Resistive
or
Reactive,
PF =
1.0 or 0.8
Continuous Industrial
grade
axial fan
Available
at both
single
and
three
phase
110-480
VAC
50/60 Hz 960*960*1400 770
KPLB-250 0 – 200 kw 1300*1200*1570 1100
KPLB-375 0 – 300 kw 1600*1200*1700 1700
KPLB-500 0 – 400 kw 1600*1400*1700 2060
KPLB-625 0 – 500 kw 2100*1560*1700 3200
KPLB-750 0 – 600 kw 2100*1560*1700 3600
KPLB-875 0 – 700 kw 2100*1560*1800 4000
KPLB-1000 0 – 800 kw 2100*1660*1900 4730
KPLB-1250 0 – 1000 kw 2200*1900*2150 5000
KPLB-2500 0 – 2000 kw 20 ft container 13200

Specifications
100-2000KW Load Bank for Generator Load Test:
1.Premium components
2.Durable and reliable
3.Easy to transport

1. Resistive type of load, PF = 1.0. Stainless steel sheathed elements manufactured from high grade magnesium oxide.
2. Rated testing voltage: AC 3P4W, 110-480V 50/60 Hz.
3. Cooling mode: Forced air-cooled, fans mounted on the side of the load bank blow horizontally. Testing power or external utility power supply for fans.
4. Working mode: Load step control
Total testing capacity ranges from 0kw to the max consisting of 10kw, 20kw, 50kw, 100kw load setting switches plus a 0-10kw fine-tuning knob. From 0kw to the max, any load combination is achievable. Load step resolution is 10kw.
5. Load bank features world-famous components to ensure reliable performance and longer service life including:
     SCHNEIDER contactors.
     Siemens switches, knobs and indicators.
     ABB Circuit breakers.
     OMRON intermediate relays.
     PHOENIX terminal blocks.
6.  Parameter measuring accuracy grade: 0.3
7. Load control accuracy: &plusmn; 5%.
8. Load bank protections: Over heating protection, cooling fans failure protection and over load protection with alarm.
9. Control mode: Two control modes available:
A)Local manual control;
B)Optional: Manual control via a remote control panel (max control distance is 30m).
10. Parameter display and measurement:
Control panel contains a LOVATO Multifunction Electricity Meter displaying voltage, current, load power, reactive power, apparent power, power factor, frequency etc.
(Optional: A professional generator tester displays and measures all sorts of steady, dynamic parameters as well as harmonic wave, can be connected to a PC for data recording and test report printing). ”
11. Operating environment:
Altitude: &le; 2500m above sea level. Ambient temp: -15~+55 ℃
Relative humidity: 95% ventilated environment without explosive or corrosive dust. Not allowed to use in rainy outdoor environment.

Any question, please contact me directly.